Water-heating boiler gas-fired RSH-600 (2х230kW)

Heat power 600 kW
Water temperature regulation range +50..+115 °C
РMax. heating agent pressure 0,6 (optionally 1,0) MPa
Fuel gas
Max.fuel consumption (natural gas) 72,0 m³/hour
Boiler water volume 140..160 L
Weight, no more 2490 kg

Характеристики

Gas-fired water-tube boiler for external installation, fully assembled inside of metal insulated block. The boiler equipped with atmospheric burner. The heat exchanger is made of finned tubes with high heat transfer surface.

Type of fuel:

  • Natural gas GOST 5542-87,
  • Liquefied petroleum gas LPG (propane-butane)

The complete set of the boiler for external installation includes:

  • boiler RSA series;
  • instruments (pressure control, water temperature control, gas low pressure control);
  • pipelines and valves.

Additional equipment for water-heating boiler is available optionally:

  • circulation pump, mesh filter (Y-strainer), safety valves;
  • methane gas contamination alarm;
  • thermal shut-off valve;
  • emergency signal transmission system via radio or to the owner's cell phone.
Heat power
       -natural gas kW 600
       -LPG kW 540
Instruments HONEYWELL VQ450M
Fuel type газ
ДInlet gas pressure before burner (natural gas):
       -minimum kPa 1
       -nominal kPa 2
       -maximum kPa
4
Inlet gas pressure before burner (LPG):
       -nominal kPa 3,7
Gas consumption max. (natural gas) m³/hour 72,0
Gas consumption min. (natural gas) m³/hour 18,0
Gas consumption nom. (LPG) m³/hour 60,0
Heating agent type  
drinking water GOST2874-73
Pressure loss in outlet pipeline after boiler
       -minimum
Pa 10
       -maximum Pa 40
Pump specification
       -model   NM-40/12A/B,"Calpeda"
       -capacity m³/hour 25,0
       -head m WC 20,0
       -power kW 2,2
       -voltage V
380
Water working pressure MPa 0,6 (optionally 1,0)
Water temperature regulation range С° +50..+115
Min. water consumption throughout the boiler (according to «boiling prevention» clause) m³/hour 25,2
Boiler water volume L 20,1140..160
Max. allowable flow resistance of heating system m WC 10
Boiler flow resistance m WC 4,0
Connection thread:
       -inlet gas connection mm DN 50
       -nozzle for heating system connection mm DN 80
Smokestack size mm DN 350 (2 шт.)
Class of fire risk ГН
Ambient class У1
Ambient temperature С° -45..+40
Efficiency, no less % 93
Weight, no more kg 2490

Item
Equipment title
   
1
Gas pipeline
mm DN80
2
Smokestack
mm DN350 (2шт.) 
3
Air inflowing gap
см² 2520
4
Inlet pipeline
mm DN80
5
Outlet pipeline
mm DN80
6
Gas vent
mm DN25
7
Boiler\’s drainage
mm DN15
8
Safety relief valve
mm Ду25 (2шт.)
B

mm 2750
L

mm 2220
H

mm 2055
B1

mm 840
B2

mm 200
B3

mm 1060
B4

mm 2970
L1

mm 1000
L2

mm 265
L3

mm 480
L4

mm 120
L5

mm 750
L6

mm 660
L7

mm 755
L8

mm 2390
H1

mm 2120
H2

mm 1360
H3

mm 180
H4

mm 1905
H5

mm 1635